GTYQ-TGD02W independent combustible gas detectorr

Model: GTYQ-TGD02W Independent Combustible Gas Detector

Working voltage: Powered by rechargeable polymer lithium batteries, with a supply voltage of 7.4V

Power:<6mW (non alarm state)

Working temperature: -20 ℃~+70 ℃

Display mode: Color LCD screen display

Detection method: continuous operation

Detection device: infrared detection type

Sampling method: natural diffusion

Detection object: Combustible gases in the air

Alarm point: Low alarm defaults to 25% LEL (adjustable), high alarm defaults to 50% LEL

Detection range: 3~100% LEL

Detection accuracy: indication deviation not exceeding ± 5% FS

Communication method: Independent default is wireless Lora communication (optional Lora communication board and communication antenna are required, with an effective communication distance of 200 meters in open and unobstructed environments).

Remote control function: optional

Output form: Passive switch quantity

Response time:<15s

Sound and light alarm function: optional

Weight: 2.5Kg

Overall size: 250 * 125 * 65mm (with sound and light)