GTYQ-TGD02W independent combustible gas detectorr
Model: GTYQ-TGD02W Independent Combustible Gas Detector
Working voltage: Powered by rechargeable polymer lithium batteries, with a supply voltage of 7.4V
Power:<6mW (non alarm state)
Working temperature: -20 ℃~+70 ℃
Display mode: Color LCD screen display
Detection method: continuous operation
Detection device: infrared detection type
Sampling method: natural diffusion
Detection object: Combustible gases in the air
Alarm point: Low alarm defaults to 25% LEL (adjustable), high alarm defaults to 50% LEL
Detection range: 3~100% LEL
Detection accuracy: indication deviation not exceeding ± 5% FS
Communication method: Independent default is wireless Lora communication (optional Lora communication board and communication antenna are required, with an effective communication distance of 200 meters in open and unobstructed environments).
Remote control function: optional
Output form: Passive switch quantity
Response time:<15s
Sound and light alarm function: optional
Weight: 2.5Kg
Overall size: 250 * 125 * 65mm (with sound and light)